NE200/300 Series Drive User Manual
Chapter 6 Parameter description 179
Choose the way of parity check. The master and the slave must keep the
same parity check setting. Otherwise, they cannot communicate normally.
0: Even parity check
1: Odd parity check
2: No parity check
Fd.04 Communication Timeout time
Range: 0.0~100.0s【0.0s】
Set communication timeout detecting time. Once establishing
communications, if there is no data communicating within timeout detection
time (Fd.04), the drive will report communication error. If Pb.03 is set to 0,
this function is disabled.
Fd.05 Response delay Range:0~500ms【5ms】
When the drive works as the slave, this parameter refers to the time
from drive receiving the host PC command to returning response frame to it.
When the drive works as the host, it refers to the interval of each broadcast
Fd.06 Communication Freq. setting
coefficient
Range:0.0~200.0%【100%】
When the frequency reference is set to be serial communication
(F0.03=4), the frequency of the drive as a slave will be the host frequency
by the coefficient defined in this parameter.
Fd.07 Communication interrupt
detection mode
Range:0~1【0】
0: Time interval between 2 packets receiving.
1: Time interval of 0005H Add. data writing