NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 59
Group F1: Start and stop control
Code
Description Setting range Default
Modify
Modbus
Address
F1.00
Start mode
0: Start directly
0 0200H
1: DC injection brake first
and then start at start freq.
Start mode
0: Start directly
1: DC injection brake first
and then start at start freq.
2: Speed tracking and start
0 0200H
F1.01
Start freq. 0.10~60.00Hz 0.50Hz
0201H
F1.02
Start freq. hold
time
0.0~10.0s 0.0s 0202H
F1.03
DC brake
current at start
G: 0.0~100.0% rated
current
0.00%
0203H
F1.03
DC brake
current at start
G: 0.0~100.0% rated
current
0.00%
0203H
P: 0.0~80.0% rated current
F1.04
DC brake time
at start
0.0
30.0s 0.0s 0204H
F1.05
Acc./Dec. mode
0:
Linear
1:
S-curve
0 0205H
F1.06
Time of S-curve
initial stage
10.0
50.0% (Acc./ Dec.
time) F1.06+F1.07≤90%
30.00%
0206H
F1.07
Time of S-curve
rising stage
10.0~80.0%
Acc./ Dec.
time
F1.06+F1.07≤90%
40.00%
0207H
F1.08
Stop mode
0: Deceleration to stop
0 × 0208H
1: Coast to stop
2: Deceleration +DC
braking
F1.09
DC brake
trigger
frequency at
stop
0.00
550.0Hz 0.00Hz
0209H