NE200/300 Series Drive User Manual
Chapter 6 Parameter description 149
F6.26 Terminal up/down initial
increment
Range:0.00~10.00kHz
【0.01Hz】
Fig.6-19 Terminal up/down initial increment
F6.27 Freq. ref. 2 datum Range: 0~1【0】
When the frequency reference 2 is analog or pulse setting, its base
frequency is defined by this parameter.
0: Maximum frequency
1: Frequency reference 1
Note: For NE200, select the frequency at 10V point as datum while this
function code is the analog.
For NE300, select the frequency datum while this function code is the
analog and pulse.
F6.28 Delay duration of X1 terminal
close
Range: 0.0~100.0s【0】
F6.29 Delay duration of X1 terminal
open
Range: 0.0~100.0s【0】
F6.30 Delay duration of X2 terminal
close
Range: 0.0~100.0s【0】
F6.31 Delay duration of X2 terminal
open
Range: 0.0~100.0s【0】