NE200/300 Series Drive User Manual
Chapter 6 Parameter description 151
F7.02 Y2 terminal output
selection
Range:0~310
F7.03 Relay 1 (TA/TB/TC) output
selection
Range: 03116
F7.04 Reserved
Range:
F7.04 Relay 2 (BRA/BRB/BRC)
output selection
Range:0~310
Multifunctional output terminal function selection details are shown in Table
6-6.
Table6-6: Multifunction output terminals selection
Value
Function Description
0 NULL
The output terminal does not have any function.
1 Run
It indicates the drive is running, and there is
output frequency (can be zero), terminal outputs
ON signal
2 Freq. arrival (FAR) Please refer to F7.05 for details.
3
Freq. level detection
1 (FDT1)
Please refer to F7.06 and F7.07 for details.
4
Freq. level detection
2 (FDT2)
Please refer to F7.08 and F7.09 for details.
5
Freq. detection when
speed-up
When the output frequency increases to the Up
detection frequency (F7.10), terminal outputs
ON signal.
6
Freq. detection when
speed-down
When the output frequency decreases to Down
detection frequency (F7.11), terminal outputs
ON signal.
7 Zero-speed running
When the drive output frequency is zero and is
still in running, the terminal outputs ON signal.
8 Zero-speed
When output frequency is zero, terminal outputs
ON signal.
9
PLC circulation
completion
When the simple PLC running completes one
cycle, the terminal outputs ON signal.