NE200/300 Series Drive User Manual
Chapter 6 Parameter description 165
Fig. 6-24 PID preset frequency and holding time
Note:
If you do not need the preset frequency function, set the preset
frequency =0.
F8.20 Enable dormancy Range: 0~1【0】
0: Disabled
1: Enabled
F8.21 Dormancy delay Range: 0~999s【120s】
F8.22 Dormancy threshold Range: 0.00~320.0Hz【20.00Hz】
F8.23 Awaken threshold Range: 0.0~100.0%【80%】
When the output frequency is lower than the dormancy threshold value
and keeps under this threshold for a lag time defined in F8.21, PID will enter
the dormant state, which means the output frequency goes to 0Hz. The
drive will quit the dormant state if PID feedback value is lower than awaken
threshold (F8.23).
F8.24 PID feedback offline
detection range
Range: 0~100.0%【0.0%】