NE200/300 Series Drive User Manual
Chapter 6 Parameter description 175
speed status.
0: Invalid
1: Acc./Dec. valid; Constant speed invalid
2: Valid all the time
FC.05 Current amplitude limit level
Range:
Type G: 80.0~200.0%160.0%
Type P: 60.0~150.0%120.0%
This parameter is used to define the current limiting level.
FC.06 Over voltage stall function Range: 021
Over voltage stall function selection.
In Drive’s Acc/Dec process, if the bus voltage exceeds the over-voltage
stall point defined by FC.07, the drive will stop Acc/Dec.
In the drives constant speed operating process, if the bus voltage
exceeds the stall overvoltage point, the drive will raise its output frequency.
The Acc/Dec time is defined by Acc/Dec time 4.
0: Invalid
1: Acc./Dec. valid; Constant speed invalid
2: Valid
FC.07 Over-voltage point for stall Range: 110.0~150.0% Bus
voltage140.0%
Define the stall over voltage point.
FC.08 Input phase loss detection
level
Range: 1100%20%
FC.09 Input phase loss detection
delay
Range: 2255s10s
Input phase loss detection function can detect loss of input phase or a