speed status.
0: Invalid
1: Acc./Dec. valid; Constant speed invalid
2: Valid all the time
FC.05 Current amplitude limit level
Range:
Type G: 80.0~200.0%【160.0%】
Type P: 60.0~150.0%【120.0%】
This parameter is used to define the current limiting level.
FC.06 Over voltage stall function Range: 0~2【1】
Over voltage stall function selection.
In Drive’s Acc/Dec process, if the bus voltage exceeds the over-voltage
stall point defined by FC.07, the drive will stop Acc/Dec.
In the drive’s constant speed operating process, if the bus voltage
exceeds the stall overvoltage point, the drive will raise its output frequency.
The Acc/Dec time is defined by Acc/Dec time 4.
0: Invalid
1: Acc./Dec. valid; Constant speed invalid
2: Valid
FC.07 Over-voltage point for stall Range: 110.0~150.0% Bus
voltage【140.0%】
Define the stall over voltage point.
FC.08 Input phase loss detection
level
Range: 1~100%【20%】
FC.09 Input phase loss detection
delay
Range: 2~255s【10s】
Input phase loss detection function can detect loss of input phase or a