NE200/300 Series Drive User Manual
198 Appendix A Modbus Communication Protocol
Appendix A NE300 Closed-loop Control
Attention:
“○”means the parameter can be changed during running.
“×”means the parameter cannot be changed during running;
“*” means the parameter is detected value or fixed value and not
changeable.
“-” means manufacturer parameter and the users have no access to it.
Parameter Brief
Code Description Setting range Default
Modify
Modbus
F0 Basic Function
F0.02
Run command control
mode
3
:
CAN 0 o 0102H
F0.03
Frequency reference1
(Freq. ref.1)
9
:
CAN
0 o 0103H
F0.04
Frequency reference1
(Freq. ref.1)
1 o 0104H
F1 Start and Stop
F1.18
Rotational speed
tracking direction
inspection
0
:
Disable
1
:
Enable
0 o 0212H
F1.19
Rotational speed
tracking direction
inspection time
10~1000ms 50ms o 0213H
F2 Auxiliary Running Function
F2.23
Instant-power-failure
freq. drop rate
1~800 300 o 0317H
F2.33
Threshold value of
Zero Freq. running
0.00~550.0Hz
(Logic is same with
EV1000/EV2000)
0.00Hz o 0321H
F2.34
Range between start
Freq. and threshold
value of Zero Freq.
0.00Hz o 0322H