NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 63
Code
Description Setting range Default Modify
Modbus
Address
for stop
3: Jog
running
F2.27
Freq. resolution
0: 0.01Hz
1: 0.1Hz 0 × 031BH
F2.28
unit
0: 0.1s 1: 0.01s
1
0
× 031CH
F2.29
High freq.
modulation mode
0: Asynchronous
modulation
0 × 031DH
1: Synchronous
modulation
F2.31
IO output Freq.
baseline select
control
0: According to the
after ACC/DEC speed
1: According to the
current value
0 ○ 031FH
F2.32
PWM
mode
0: uplink 16Hz discrete
modulation mode
(5-stage mode),
downlink 12Hz
continuous modulation
mode (7-stage mode)
1: fixed as z continuous
modulation mode
(7-stage mode)
0 ○ 0320H
F2.33
Threshold value
of Zero Freq.
running
0.00~550.0Hz 0.00Hz ○ 0321H
F2.34
Range between
start Freq. and
threshold value
of Zero Freq.
0.00~550.0Hz 0.00Hz ○ 0322H
Group F3: Vector Control Parameters
Code
Description Setting range Default Modify
M