Chapter 6 Parameter description 107
F0.17 Keypad direction Range: 0~10
This parameter is used to select the motor rotation direction when the
drive running command channel is keypad.
0: Forward rotation
1: Reverse rotation
F0.18 Motor wiring direction Range: 0~10
The drive output FWD direction might be different from FWD direction of
motor. User can change the motor phases wiring sequence or change this
parameter to make them agree with each other.
0: Positive sequence
1: Reversed sequence
F0.19 Acc. time1 Range: 0.13600sDepend on
model
F0.20 Dec. time1 Range: 0.13600sDepend on
model
Acceleration time: The time that the drive accelerates from 0Hz to
maximum output frequency (F0.11).
Deceleration time: The time that the drive decelerates from maximum
frequency (F0.11) to 0Hz.
This series drive has defined 4 types of Acc/Dec time. Here, Acc/Dec
time 1 is defined, and Acc/Dec time 2~4 can be defined in F2.03F2.08.
User can select different Acc/Dec time by external multifunction input
terminal. Acc.1/Dec.1 is taken as default.