NE200/300 Series Drive User Manual
160 Chapter 6 Parameter description
2: AI2 terminal
Taken as 0 ~ 10V analog voltage or 0 ~ 20mA current input, which can
be selected by DIP switch setting.
3: Pulse input
4: Serial communication
The input value should in 0~100.00% (0~10000). 100.00% corresponds
to the full scale of PID.
Note:
The relationship between AI1, AI2 & pulse frequency and the actual
physical quantities can be seen in F6.10 ~ F6.26. Its full range (100.0%) of
actual physical quantities correspond to the PID full range
F8.01 PID feedback channel
selection
Range: 0~7【1】
This parameter defined the PID feedback channel。
0: AI1 terminal
Taken as 0~10V analog voltage input.
1: AI2 terminal
Taken as 0 ~ 10V analog voltage or 0 ~ 20mA current input, which can
be selected by DIP switch setting.
2: Pulse input
3: serial communication
The input value should in 0~100.00% (0~10000). 100.00%
corresponds to the full scale of PID.
4: AI1-AI2
AI1-AI2 as PID feedback, if the result is negative the feedback value is
negative
5: AI1+AI2
AI1+ AI2 as PID feedback, if the result is bigger than the actual