NE200/300 Series Drive User Manual
Chapter 6 Parameter description 171
4: Pulse input
6.11 Wobble frequency running group (FA)
The wobble frequency running function is to make the drive output
frequency wobbling up and down with the setup frequency as the center.
The trace of running frequency at the time axis is shown in Figure 6-26, of
which the swing amplitude is set by FA-00.When FA-00 is set to 0, indicating
the swing amplitude is 0, the wobble frequency function is disabled.
Fig.6-26 Wobble frequency running diagram
FA.00 Wobble frequency amplitude
Range: 0.0~50%【0.0%】
FA.01 Jitter frequency Range: 0.0~50% (Relative to
FA.00) 【0.0%】