Unidrive M702 / HS72 Control Getting Started Guide 15
Issue Number: 4
Safety information Introduction Control connections Getting started
Basic parameters
(Menu 0)
Running the motor Further information
6. Select ‘Save parameters in drive’ to perform a parameter save.
The drive is now ready to run.
Action Detail
Motor Setup
Unidrive M Connect contains a database for induction motors and permanent magnet motors.
Provision is also made to enter motor nameplate data.
The next section describes the use of the motor database for a Leroy Somer LSRPM motor
used in RFC-S Sensorless mode.
Motor Feedback
Setup
This only needs to be performed in RFC-A (with feedback) mode
Set Pr 03.024 = Feedback (0)
Enter:
Encoder power supply in Pr. 03.036 = 5 V (0), 8 V (1) or 15 V (2).
If output voltage from the encoder is >5 V, then the termination resistors must be
disabled Pr 03.039 to 0.
Drive encoder Lines Per Revolution (LPR) in Pr 03.034 (set according to encoder)
Drive encoder termination resistor setting in Pr 03.039:
0 = A-A\, B-B\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled
Motor Thermistor
Set-up
The motor thermistor connection may be made either:
Through the drive encoder port (terminal 15)
Select thermistor type in P1 Thermistor Type (03.118)
•Set P1 Thermistor Fault Detection (
03.123
) to either Temperature (1) or Temp or Short (2)
Through terminal 8 (Digital Input 5 / Analog Input 3) of the control terminals (requires a drive
with date code 1710 or later and control firmware V01.13.00.00 or later).
Change Analog Input 3 Mode (07.015) from Disable (0) to either Therm Short Cct (7) or
Thermistor (8).
Select the thermistor type in Analog Input 3 Thermistor Type (07.046)
Ramps Setup
Enter the required Acceleration rate and Deceleration rate
Note: If a braking resistor is installed, set 'Ramp mode' to 'Fast'. Also ensure Pr 10.030 and
Pr 10.031 and Pr 10.061 are set correctly, otherwise premature 'Brake R Too Hot' trips may
be seen).
Autotune
Not required when using data from the motor database for a Leroy Somer LSRPM motor used
in RFC-S Sensorless mode.
NOTE
Setting the encoder voltage supply too high for the encoder could result in
damage to the feedback device.
CAUT ION