Unidrive M200 / M201 Control User Guide 131
Issue Number: 2
C.OPt NV Media Card trip; option module installed is different between source drive and destination drive
180
The C.OPt trip indicates that parameter data is being transferred from the NV Media Card to the drive, but the option
module category is different between the source and destination drives. This trip does not stop the data transfer, but is a
warning that the data for the option module that is different will be set to the default values and not the values from the card.
This trip also applies if a compare is performed between the data block on the card and the drive, and the option module
fitted is different between the source and target.
Recommended actions:
• Ensure the correct option module is installed.
• Press the red reset button to acknowledge that the parameters for the option module installed will be at their
default values
• This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive.
C.Pr NV Media Card data blocks are not compatible with the drive derivative
175
The C.Pr trip is initiated either at power-up or when the card is accessed, If Drive Derivative (11.028) or Product Type
(11.063) are different between the source and target drives. This trip can be reset and data can be transferred in either
direction between the drive and the card.
Recommended actions:
• Use a different NV Media Card
• This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive
• Choose a file compatible between the source and target drives, if sub-trip 2.
C.rdo NV Media Card has the Read Only bit set
181
The C.rdo trip indicates that an attempt has been made to modify data on a read-only NV Media Card or to modify a read-
only data block. A NV Media Card is read-only if the read-only flag has been set.
Recommended actions:
• Clear the read only flag by setting Pr 00 to 9777 and reset the drive. This will clear the read-only flag for all data blocks
in the NV Media Card
C.rtg NV Media Card Trip; The voltage and / or current rating of the source and destination drives are different
186
The C.rtg trip indicates that parameter data is being transferred from the NV Media Card to the drive, but the current and /
or voltage ratings are different between source and destination drives. This trip also applies if a compare (using Pr 00 set to
8yyy) is performed between the data block on a NV Media Card and the drive. The C.rtg trip does not stop the data transfer
but is a warning that rating specific parameters with the RA attribute may not be transferred to the destination drive.
Recommended actions:
• Reset the drive to clear the trip
• Ensure that the drive rating dependent parameters have transferred correctly
• This trip can be suppressed by setting Pr 00 to 9666 and resetting the drive.
C.SL NV Media Card trip; Option module file transfer has failed
174
The C.SL trip is initiated, if the transfer of an option module file to or from a module failed because the option module does
not respond correctly. If this happens this trip is produced with the sub-trip number indicating the option module slot
number.
C.tyP NV Media Card parameter set not compatible with current drive mode
187
The C.tyP trip is produced during a compare if the drive mode in the data block on the NV Media Card is different from the
current drive mode. This trip is also produced if an attempt is made to transfer parameters from a NV Media Card to the
drive if the operating mode in the data block is outside the allowed range of operating modes, for the target drive.
Recommended actions:
• Ensure the destination drive supports the drive operating mode in the parameter file.
• Clear the value in Pr 00 and reset the drive
• Ensure destination drive operating mode is the same as the source parameter file
Trip Diagnosis
Sub-trip Reason
1
If Drive Derivative (11.028) is different between the source and target drives. This trip is initiated either
at power-up or when the SD card is accessed. This trip can be reset and data can be transferred in
either direction between the drive and the card.
2
If Product Type (11.063) is different between the source and target drives or the file is corrupted or
incompatible. This trip is initiated either at power-up or when the SD card is accessed. This trip can be
reset but no data are transferred in either direction between the drive and the card.