10.4 Ethernet sub trip codes
If the Ethernet interface detects an alarm condition during operation, it will set the appropriate bit in
Active Alarm Bits MM.009. Table 10-4 Ethernet alarm bits on page 205 shows the possible
conditions.
Table 10-4 Ethernet alarm bits
10.5 Ethernet hardware fault trip codes
If the Ethernet interface detects an internal hardware error, it will force a SlotX.HF (code 250) trip
on the drive with an appropriate sub trip string. Table 10-5 shows the possible error codes and sub
trip strings.
Table 10-5 Ethernet hardware fault trip codes
Recommended actions:
Ensure the option module is installed correctly.
Replace the option module.
Replace the drive.
Bit
(Pr MM.009)
Alarm Description
0 User Program The user program has generated an alarm
1 eCMP An eCMP alarm has been generated
2 Modbus A Modbus alarm has been generated
3 Ethernet/IP An Ethernet/IP alarm has been generated
4 Reserved Reserved
5 File System File system full alarm has been generated
6 Too Hot Temperature too high alarm has been generated
Value
Pr 0.10.070
Reason
1 The module category cannot be identified
2
All the required customisable menu table information has not been supplied or the
tables supplied are corrupt
3
There is insufficient memory available to allocate the comms buffers for this module
4 The module has not indicated that it is running correctly during drive power-up
5
The module has been removed after power-up or it has ceased to indicate to the
drive processor that it is still active
6
The module has not indicated that it has stopped accessing drive parameters
during a drive mode change
7
The module has failed to acknowledge that a request has been made to reset the
drive processor
8
The drive failed to read correctly the menu table from the module during drive power-up
9 The drive failed to upload menu tables from the module and timed-out (5s)
10 Menu table CRC invalid

Table of Contents