100 SI-Ethernet User Guide
Issue: 3
This parameter is used to display the error code if an EtherNet/IP configuration error occurs.
This parameter shows the EtherNet/IP cyclic data transfer rate.
S.20.004 Configuration error
Minimum 0
(Display: No error)
Maximum
8
(Display: Out cons trig pr)
Default None Units None
Type 8 Bit Volatile Update Rate Background
Display Format None Decimal Places 0
Coding RO, Txt, ND, NC, PT, BU
Value Text Description
0 No error No error
1 RPI event dst RPI timeout event destination not valid
2 RPI event type RPI timeout event type not valid
3 IDLE event dst PLC IDLE event destination not valid
4 IDLE event type PLC IDLE event type not valid
5 Input mapping Input mapping parameter not valid
6 Output mapping Output mapping parameter not valid
7 In cons trig pr Input consistency trigger parameter not valid
8 Out cons trig pr
Output consistency trigger parameter not valid
S.20.007 Cyclic Data Transfers / s
Minimum 0 Maximum 65535
Default None Units Messages/s
Type 16 Bit Volatile Update Rate Background
Display Format None Decimal Places 0
Coding RO, ND, NC, PT, BU