5 Parameter
BU 0800 en-4521 107
P559 DC run-on time S P
{ 0.50 }
After a stop signal and elapse of the brake ramp, direct current is applied to the motor
for a short time. This should completely stop the drive. Depending on the inertia, the
time for which the current is applied can be set in this parameter.
The current level depends on the previous braking procedure (current vector control)
or the static boost (linear characteristic).
P560 Parameter, Saving mode S
If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles to the EEPROM (100,000 x) is not
exceeded.
Value Meaning
0 Only in RAM
Changes to the parameter settings are not written to the EEPROM.
All saved settings which were made before changing the saving
mode are retained, even if the FI is disconnected from the mains.
1 RAM and EEPROM
All parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the
mains supply.
Saving in RAM and EEPROM not possible. (No parameter changes
are adopted)
P583 Motor phase sequence S P
The motor phase control sequence (U – V – W) can be changed with this parameter.
This enables the direction of rotation of the motor to be changed without changing the
motor connections.
If there is a voltage on the output terminals (U – V – W) (e.g. on enabling) the
parameter setting or the parameter set may be changed by setting parameter P583.
Otherwise the frequency inverter switches off with error message E016.2.
Value Meaning
1 Inverted
“Invert motor phase sequence” The direction of rotation of the
motor is changed. The counting direction of the encoder for speed
detection (if present) remains unchanged.
As for setting {1}, however in addition the counting direction of the
encoder is changed.