NORDAC ON / ON+ (SK 3xxP) – Manual with installation instructions
128 BU 0800 en-4521
The motor switch-off limit is reached.
• Reduce motor load
• Check system for blockage or overload
Further notes:
• Check settings P534 [-01]
The machine drives the motor and puts it into generator
operation. Warning: 80% of the generator switch-off limit
have been reached.
• Reduce (generator) motor load
• Check system for overload
Further notes:
• Check settings P534 [-02]
Overshooting or undershooting of permissible load torques
(P525 … P529) for half of the time set in (P528).
• Adjust load
Further notes:
• Change limit values (P525 … P527)
• Increase delay time (P528)
• Change monitoring mode (P529)
Universal encoder warning
The universal encoder issues a warning to the FI