NORDAC ON / ON+ (SK 3xxP)Manual with installation instructions
128 BU 0800 en-4521
C012
12.1
Limit moto./Customer
The motor switch-off limit is reached.
Reduce motor load
Check system for blockage or overload
Further notes:
Check settings P534 [-01]
C012
12.2
Limit gen.
The machine drives the motor and puts it into generator
operation. Warning: 80% of the generator switch-off limit
have been reached.
Reduce (generator) motor load
Check system for overload
Further notes:
Check settings P534 [-02]
C012
12.3
Torque limit
- -
C012
12.5
Load monitor
Overshooting or undershooting of permissible load torques
(P525 … P529) for half of the time set in (P528).
Adjust load
Further notes:
Change limit values (P525 … P527)
Increase delay time (P528)
Change monitoring mode (P529)
C025
25.4
Universal encoder warning
The universal encoder issues a warning to the FI