NORDAC ON / ON+ (SK 3xxP)Manual with installation instructions
18 BU 0800 en-4521
1.7 Standards and approvals
All devices across the entire series comply with the standards and directives listed below.
Approval Directive
Applied
standards
Certificates Label
CE
(European
Union)
Low Voltage 2014/35/EU
EN 61800-5-1
EN 60529
EN 61800-3
EN 63000
EN 61800-9-1
EN 61800-9-2
C310001_0921
EMC 2014/30/EU
RoHS 2011/65/EU
Delegated directive
(EU)
2015/863
Ecodesign 2009/125/EC
Regulation (EU)
Ecodesign
2019/1781
UL
(USA)
UL 61800-5-1 E171342
CSA
(Canada)
C22.2 No.274-13 E171342
RCM
(Australia)
F2018L00028 EN 61800-3 ------
EAC
(Eurasia)
TR CU 004/2011,
TR CU 020/2011
IEC 61800-5-1
IEC 61800-3
EA-----
Table 2: Standards and approvals
1.7.1 UL and CSA approval
File No. E171342
The categorisation of protective equipment approved by the UL according to United States standards
for the devices described in this manual is listed below, basically with the original wording. The
categorisation of the individually relevant fuses or circuit breakers can be found in the “Electrical Data”
section of this manual.
All devices have a parameterisable motor overload protection (see P533, P535). UL recognised
(7.2.1).
Conditions UL/CSA according to report
Information
• “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the Manufacturer Instructions, National Electrical Code and any
additional local codes”.
CSA: For Canada: Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Canadian Electrical Code, Part I”.
“Use 60 °C Copper Conductors Only”, or “Use min. 60°C rated Copper Conductors Only”, or equivalent.
“For use in Pollution Degree 2 and Overvoltage Category III environments only”, or equivalent.
Maximum Surrounding Air Temperature 40°C.”
“The source shall be derived from a non-corner grounded type TN or IT AC source not exceeding 277 V
phase to earth”, or equivalent.