EasyManua.ls Logo

Nord Drivesystems SK 300P Series - Diagnostic Connection

Nord Drivesystems SK 300P Series
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Assembly and installation
BU 0800 en-4521 39
2.7 Diagnostic connection
The frequency inverter is equipped with an RJ12 diagnostic interface (1). Either a PC, a Bluetooth
stick or a manual control unit can be connected here via RS 232/ RS 485.
Communication
interface
Device connected to different communication tools
24 VDC ± 20%
RS 485 (For connecting a parametrisation box)
9600 … 38400 Baud
Terminating resistance (1 kΩ) fixed
RS 232 (For connecting to a PC (NORD CON))
9600 … 38400 Baud
1
RS485 A+
Data cable RS485
P502…
2
RS485 B-
Data cable RS485
P513 [-02]
3
GND
Reference potential of bus
signals
4
RS232 TXD
Data cable RS232
5
RS232 RXD Data cable RS232
6
+24 V
Voltage output
1 - 2 - 3 - 4 - 5 - 6

Table of Contents