NORDAC ON / ON+ (SK 3xxP) – Manual with installation instructions
60 BU 0800 en-4521
5.1.2 Basic parameters
P100 Parameter set S
Selection of the parameters sets to be parameterised. Four parameter sets are
available. The parameters to which different values can also be assigned in the four
parameter sets are known as “parameter set-dependent” and are indicated with a “P”
in the header in the following descriptions.
The operating parameter set is selected via correspondingly parametrised digital
inputs or BUS actuation.
If enabling is via the keyboard of a ParameterBox, the operating parameter set
corresponds to the settings in P100.
P101 Copy parameter set S
{ 0 }
“Copy parameter set”. By confirmation with the OK key, the active parameter set (set
in P100) is copied into the selected parameter set.
Value Meaning
No copy process triggered.
Copies the active parameter set to parameter set 1
2 Copy actual to P2
Copies the active parameter set to parameter set 2
3 Copy actual to P3
Copies the active parameter set to parameter set 3
Copies the active parameter set to parameter set 4
P102 Acceleration time P
The acceleration time is the time which corresponds to the linear frequency increase
from 0 Hz to the set maximum frequency P105. If an actual setpoint of <100 % is
being used, the acceleration time is reduced linearly according to the setpoint which
has been set.
The acceleration time can be extended by certain circumstances, e.g. FI overload,
setpoint delay, ramp smoothing, or if the current limit is reached.
Care must be taken that the parameter values are realistic. The setting
is
not permissible for drive units!
Ramp gradient:
Amongst other things, the ramp gradient is governed by the inertia of the rotor. A ramp
with a gradient which is too steep may result in “breakdown” of the motor.
Extremely steep ramps (e.g.: 0 – 50 Hz in < 0.1 s) should be avoided, as this may
cause damage to the frequency inverter.