NORDAC ON / ON+ (SK 3xxP)Manual with installation instructions
82 BU 0800 en-4521
P351 PLC set val. select.
Setting range
0 … 3
Factory setting
{ 0 }
Description
Selection of the source for the control word (CTW) and the main setpoint (MSW) with
active PLC functionality P350 = {1}). With the settings P351 ={0} and {1} the main
setpoints are defined via P553, but the definition of the auxiliary setpoints remains
unchanged via P546. This parameter is only adopted if the frequency inverter is in
"Ready for switch-on" status.
Setting values
Value Meaning
0
STW & HSW = PLC
The PLC provides the control word (CTW) and the main setpoint
(MSW) Parameters P509 and P510 [-01] have no function.
1
CTW = P509
The PLC provides the main setpoint (MSW) The control word
source (CTW) corresponds to the setting in parameter P509.
2
MSW = P510[1]
The PLC provides the control word (CTW) The source for the main
setpoint (MSV) corresponds to the setting in parameter P510[-01].
3
CTW & MSW = P509/510
The source for the control word (CTW) and the main setpoint
(MSW) corresponds to the setting in parameter P509 / P510 [-01].
P355 PLC integer setpoint
Setting range
-32768 … 32767
Arrays
[-01] … [-10]
Factory setting
All Arrays: { 0 }
Description
Data can be exchanged with the PLC via this INT array. This data can be used by the
appropriate process variables in the PLC.
P356 PLC long setpoint
Setting range
-2 147 483 648 … 2 147 483 647
Arrays
[-01] … [-05]
Factory setting
All Arrays: { 0 }
Description
Data can be exchanged with the PLC via this DINT array. This data can be used by
the appropriate process variables in the PLC.
P360 PLC display value
Display range
- 2 147 483.648 … 2 147 483.647
Arrays
[-01] … [-05]
Description
Display of PLC data. By means of the relevant process variables, the parameter
arrays can be written by the PLC. The values are not saved!
P370 PLC status
Display range
0000 … FFFF
(hex)
0000 0000 … 1111 1111
(bin)
Description
Display of the actual PLC status.
Display values
Value (Bit) Meaning
0
P350=1
P350 has been set to the function “Activate internal PLC”.
1 PLC active
The internal PLC is active
2 Stop active
The PLC program is set to “Stop”
3
Debug active
Debugging of the PLC program is running.
4
PLC error
The PLC has an error.
However, PLC user errors 23.xx are not displayed here.
5 PLC stopped
The PLC program has been stopped (single step or breakpoint)
6
Scope Memory in use
A function block uses the memory area for the oscilloscope function of
the NORDCON software. The oscilloscope function cannot be used.