NORDAC ON / ON+ (SK 3xxP) – Manual with installation instructions
84 BU 0800 en-4521
P415 PID control D comp. S P
This parameter is only effective when the function
“PID current freq.”
The D-component of the PID controller determines the frequency change depending
on time.
P416 Ramptime PI setpoint S P
Ramptime PI setpoint
". This parameter is only effective when the function
“PID actual
frequency” is selected.
Ramp for PI setpoint
P420 Digital inputs
Digital input 1 (DIN1) integrated into the FI
Digital input 2 (DIN2) integrated into the FI
[-03] = Digital input 3 Digital input 3 (DIN3) integrated into the FI
Digital input 4 (DIN4) integrated into the FI
[-08] = Reserved
Digital input functions
". Up to 4 inputs which can be freely programmed with digital
functions are available.
Value Description Signal
00 No function Input switched off. ---
01 Enable right
The FI delivers an output signal with the rotation field “Right” if a
positive setpoint is present. 0 → 1 Flank (P428 = 0)
high
The FI delivers an output signal with the rotation field “Left” if a
positive setpoint is present. 0 → 1 Flank (P428 = 0)
If the drive is to start up automatically when the mains is switched on (P428 = 1), a permanent High level for
enabling must be provided (bridge between DIN 1 and the control voltage output). If the functions “Enable
right” and “Enable left” are actuated simultaneously, the device is blocked.
If the device is in fault status but the cause of the fault no longer exists, the error message is acknowledged
with a 1 → 0 flank.
Causes the rotation field to change direction (combined with
Enable right or left).
The frequency from P429 is added to the actual setpoint.
The frequency from P430 is added to the actual setpoint.
06 Fixed frequency 3
1)
The frequency from P431 is added to the actual setpoint. high
07 Fixed frequency 4
The frequency from P432 is added to the actual setpoint. high
First bit of the parameter set switching; selection of the active
parameter set 1…4 (P100).
During the acceleration or deceleration phase, a Low level will
cause the actual output frequency to be “maintained”. A High
level allows the ramp to continue.
10 Voltage disable
The frequency inverter output voltage is switched off; the motor
runs down freely.
low
11 Quick stop
The FI reduces the frequency according to the quick stop time
from P426.
low