5 Parameter
BU 0800 en-4521 93
P482 Norm. BusIO Out Bits S
Setting range
-400 … 400%
Arrays
[-01] = BusIO Out Bit 0
Out Bit 0 … 3 via Bus
[-02] =
BusIO Out Bit 1
[-03] =
BusIO Out Bit 2
[-04] =
BusIO Out Bit 3
[-05] =
BusIO Out Bit 4
Out Bit 4 … 5 via Bus
[-06] = BusIO Out Bit 5
[-07] =
BusIO Out Bit 6
Out Bit 6 … 7 via Bus
[-08] =
BusIO Out Bit 7
[-09] =
Marker 1
See "Use of markers" at the end of the description
of parameter P481.
[-10] =
Marker 2
[-11] = Bit 10 Bus status word
Bit 1013 of the status word.
[-12] =
Bit 13 Bus status word
Factory setting
All { 100 }
Description
"Normalisation of Bus IO Out Bits". Adjustment of the limit values of the Bus Out Bits.
For a negative value, the output function will be output negative.
Reference to the following values:
Current limit (P481 = 3) =
x [%]
P203
“Nominal current"
Torque current limit (P481 = 4) =
x [%] P203 P206 (calculated nominal
motor torque)
Frequency limit (P481 = 5) =
x [%] P201 “Nominal frequency”
P483 Hyst. BusIO Out Bits S
Setting range
1 … 100%
Arrays
[-01] =
BusIO Out Bit 0
Out Bit 0 … 3 via Bus
[-02] =
BusIO Out Bit 1
[-03] = BusIO Out Bit 2
[-04] =
BusIO Out Bit 3
[-05] =
BusIO Out Bit 4
Out Bit 4 … 5 via Bus.
[-06] =
BusIO Out Bit 5
[-07] =
BusIO Out Bit 6
Out Bit 6 … 7 via Bus.
[-08] = BusIO Out Bit 7
[-09] =
Marker 1
See "Use of flags" at the end of the description of
parameter P481.
[-10] =
Marker 2
[-11] =
Bit 10 Bus status word
Bit 10 … 13 of the status word.
[-12] =
Bit 13 Bus status word
Factory setting
All { 10 }
Description
"Hysteresis Bus IO Out Bits". Difference between switch-on and switch-off point to
prevent oscillation of the output signal.