Pos: 29 8 /Anlei tung en/El ektr onik/S afety /7. Mel dung en zum Betr iebsz usta nd/Fe hler E018 "Sic herhei tskr eis" [S K 500P] @ 44\mod_1594806764103_388.docx @ 2646451 @ @ 1
(SafetyCirc)
The Safe Pulse Block safety circuit has triggered during
release.
The parameterised trigger time (P423) of the SS1-t
functionality has expired. STO is triggered as the inverter
still sends output pulses.
This error cannot be acknowledged. Restart the frequency
inverter (Power Off 120 s Power On).
A malfunction has occurred in the safety function.
• Restart the inverter.
• If the fault recurs, read out the extended error number in
the parameter “Actual Operating Status (P700 [-04]) and
contact Support.
Pos: 299 /A nleit ung en/El ek tr onik /Saf ety /7. M el dung en zum Betr ie bsz usta nd/ Fehl er E11 0 "S afe ty CR C" [SK 500 P] @ 4 4\mod_1593162805892_388.docx @ 2638594 @ @ 1
A malfunction has occurred in the safety function.
• The CRC checksum does not match the safety
parameters “Safety SS1 max. time” (P423) and “Safe
Dig.input” (P424) and must be adjusted.
The CRC checksum has been changed. The changes are
only adopted after a restart.
protection required
For use of the Safety Digital Input, the parameter password
protection “Change safety passw.” (P498) must be set.
When changing the parameterisation of the safe input, the
password in the “Safety password” parameter (P497) must
be set.
Pos: 30 1 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum Betr iebsz usta nd/Mel dunge n Eins chalts perr e (Tabel lenü berschr ift) @ 3\mod_1361803467385_388.docx @ 59922 @ 5 @ 1