3 Assembly and installation
BU 0630 en-2020 29
Remove the control
terminals and blank
cover.
Remove the STO
contact jumper.
Install the SK CU5-STO
customer unit.
Install the control
terminals and blank
cover.
Pos: 12 6 /Anlei tu nge n/El ektr onik /S afety /4 . M ontag e u nd I nst all ati on/ Elek tri sch er Ans chl uss _0 1 @ 15\mod_1485429904375_388.docx @ 2316246 @ 2 @ 1
3.2 Electrical connection
The information for installation or electrical connection from the manual BU 0600 as well as all of the
following information must be observed.
Pos: 12 7 /Anlei tung en/El ektr onik/FU und Star ter/1 . Allg emei nes/Sic herh eits- und Ins tall ations hinwei se un d Warn- G efa hren hinw eise /Sic her heit shi nwei se (a usla ufe nd)/ vers chie den e/W ARNU NG - Elek tris cher Sc hlag ( nich t un ter Spa nnu ng ar bei te n) @ 14\m od_1480331381423_388.docx @ 2308485 @ @ 1
WARNING
Electric shock
Touching electrically conducting components may cause an electric shock and severe or possibly fatal injury.
Disconnect the frequency inverter from the power supply before starting installation work.
Only work on devices which have been disconnected from the power supply.
Pos: 12 8 /Anlei tung en/El ektr onik/FU und Star ter/1 . Allg emei nes /Sic herh eits - und I nstall atio nshinw eise un d Warn- Gefa hre nhi nw eise /Sic her hei tshi nw eise (a usla ufe nd)/ vers chi ed ene/W AR NUN G - El ektri scher Schlag (Wartez eit) @ 14\mod_1480332099956_388.docx @ 2308520 @ @ 1
WARNING
Electric shock
The frequency inverter carries hazardous voltage for up to 5 minutes after being switched off.
Only start work after a waiting period of at least 5 minutes after switching off the mains supply
(disconnection).
Pos: 13 0 /Anlei tung en/El ektr onik/S afety /4. Mon tage u nd I nst all ati on/ Ver draht ung sri chtl ini en [ BU0 630] @ 44\mod_1593153830132_388.docx @ 2638326 @ 3 @ 1
3.2.1 Wiring guidelines
Wire end sleeves must be used if flexible cables (multiple strand or fine-wire) are used for the
connections X19 (at position X17) or X20. In addition, the wiring guidelines in the frequency inverter
manual (BU 0600) also apply.
Pos: 132 /A nleit ung en/El ek tr onik /Saf ety /4. M on tage un d I nstal la tio n/Net za nschl uss [B U0 630] @ 4 0\mod_1578408046098_388.docx @ 2582167 @ 3 @ 1
3.2.2 Mains connection
Devices for implementation of a safety function must only be operated on TN, TT and IT networks.
Grounded Corner operation is not intended.
For operation in IT networks
the IT network screws must be removed
a braking resistor must be used