NORDAC PRO (SK 500P) – Users Manual for Frequency Inverters
180 BU 0600 en-2319
The LED labelled "BUS" indicates the status of communication at the system bus level.
Status Meaning
• No process data communication
• Process data communication active
Flashing green (0.5 Hz) • FI is in standby but not enabled
• Monitoring error P120 or P513 ( E10.0/E10.9)
Flashing red (1 Hz) • Field bus interface telegram timeout (E10.2/E10.3)
• System bus in state “Bus off”
The LED labelled "USB" indicates the status of the USB connection.
Status Meaning
• No communication via USB
Lights up green • USB connection active
ControlBox Display
The ControlBox displays an error with its number and the prefix "E". In addition, the present fault can
be displayed in array element [-01] of parameter (P700). The last error messages are stored in
parameter (P701). Further information about the frequency inverter status at the moment of the fault
can be obtained from parameters (P702) to (P706) / (P799)
If the cause of the error is no longer present, the error display in the ControlBox flashes and the error
can be acknowledged with the Enter key.
In contrast, warning messages are prefixed with "C" ("Cxxx") and cannot be acknowledged. They
disappear automatically when the reason for them is no longer present or the frequency inverter has
switched to the "Error" state. Display of the message is suppressed if the warning appears during
parameterisation.
The present warning message can be displayed in detail at any time in array element [-02] of
parameter (P700).
The reason for an existing disabled switch on cannot be displayed with the ControlBox.
ParameterBox display
The ParameterBox displays the messages in plain text.