6 Operating status messages
BU 0600 en-2319 181
6.2 Messages
Error messages
Display in the
SimpleBox / ControlBox
Fault
Text in the ParameterBox
Cause
• Remedy
Group Details in P700
[-01] / P701
E001 1.0 Overtemp. Inverter
"Inverter overtemperature"
(inverter heat sink)
Inverter temperature monitoring
measurements are outside of the permissible temperature
range, i.e. the error is triggered if the permissible lower limit
is undershot or the permissible upper temperature limit is
exceeded.
•
Depending on the cause: Reduce or increase the
ambient temperature
•
Check the FI fan / control cabinet ventilation
• Check the FI for dirt
1.1 Overtemp. FI internal
"Internal FI overtemperature"
(interior of FI)
E002 2.0 Overtemp. Motor PTC
"Overtemperature motor
thermistor "
Motor temperature sensor (PTC) has triggered
• Reduce motor load
• Increase motor speed
• Use external motor fan
2.1 Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
I
2
t motor has triggered (calculated overtemperature of
motor)
• Reduce motor load
• Increase motor speed
2.2 Overtemp. Brake r.ext
"Overtemperature of external
brake resistor "
Overtemperature via digital
input (P420 […])={13}
Temperature monitor (e.g. brake resistor) has activated
• Digital input is Low
• Check connection, temperature sensor