NORDAC PRO (SK 500P) – Users Manual for Frequency Inverters
194 BU 0600 en-2319
7.2.2 Electrical data 400 V
type
SK 5xxP…
-250-340- -370-340- -550-340- -750-340- -111-340-
Nominal motor power
(4-pole standard motor)
400 V
0.25 kW 0.35 kW 0.55 kW 0.75 kW 1.1 kW
3
3 AC 380 … 480 V, -20 % / +10 %, 47 … 63 Hz
Input current
rms
1.1 A 1.3 A 1.8 A 2.3 A 3.3 A
Output voltage 400 V
3 AC 0 – Mains voltage
Output current
Min. brake resistance Accessories
390 Ω 300 Ω 390 Ω 300 Ω 220 Ω
Pulse frequency
Range
4 – 16 kHz
Max. ambient temperature S1
40 °C 40 °C 40 °C 40 °C 40 °C
Type of ventilation
Free convection
Fan,
temperature
controlled
Switching
thresholds:
1)
ON = 57 °C,
OFF = 47 °
General fuses (AC) (recommended)
1) Short test run after connection of the mains voltage