NORDAC PRO (SK 500P) – Users Manual for Frequency Inverters
70 BU 0600 en-2319
Parameter settings (Analogue input 2)
The following parameters must be set for the function of the KTY84-130.
The motor data P201-P207 must be set according to the rating plate.
The motor stator resistance P208 is determined at 20 °C with P220 = 1.
Analogue input function 2, P400 [-02] = 48
(motor temperature)
Analogue input 2 mode, P401 [-02] = 1 (negative temperatures are also measured)
Adjustment of analogue input 2: P402 [-02] = 1,54 V and P403 [-02] = 2,64 V
(for R
V
= 2,7 kΩ)
Adjust time constants: P161 [-02] = 400ms (Filter time constant is at maximum)
Parameter P161 is a module parameter. This cannot be set on the frequency inverter, but must be set directly on the I/O module.
Communication is carried out e.g. by directly connecting a ParameterBox to the RS232 interface of the module, or by connection to the
frequency converter via the system bus.
(Parameter P1101 object selection → … )
7. Motor temperature control (display): P739 [-03]