NORDAC PRO (SK 500P) – Users Manual for Frequency Inverters
78 BU 0600 en-2319
5.1.1 Operating display
P000 Operating display
The operating value selected in parameter P001 is displayed.
Important information about the operating status of the drive can be read out as
required.
P001 Selection of display value
Factory setting { 0 }
Selection of the operating display for display via 7-segment display.
Display values
Value Meaning
0 Actual frequency [Hz] Present supplied output frequency
1 Speed [rpm] Calculated speed
Output frequency that corresponds to the present setpoint. This
need not correspond with the current output frequency.
Present measured output current
4 Torque current [A] Torque-forming output current
5 Voltage [V AC] Present AC voltage at the device output
6 Link voltage [V DC]
The "Link circuit voltage is the internal FI DC voltage. Amongst
other things, this depends on the level of the mains voltage.
7 cos Phi [-] Calculated value of actual power factor
Calculated value of actual apparent power
Calculated value of actual effective power
10 Torque [%] Calculated value of actual torque
11 Field [%] Calculated value of actual rotating field in the motor
Time for which mains voltage has been present on the device
"Enabled operating hours" is the time for which the device has
been enabled.
Actual value present at analogue input 1 of the FI
15 Analogue input 2 [%] Actual value present at analogue input 2 of the FI
16 … 18 Reserved, POSICON
Actual temperature of heat sink
Average motor load based on known motor data P201 … P209
21 Brake load R [%]
"Braking resistor load" is the average load on the braking resistor
based on the known resistance data P556 … P557
22 Ambient UZW temp. [°C] Actual interior temperature of the FI
23 Motor temperature measured via temperature sensor (KTY-84, PT100, PT1000)
24 … 29 Reserved
"Actual motor potentiometer setpoint with saving": P420 … = 71/72.
With this function the setpoint can be read out or pre-set (without
the drive running).
31 … 39 Reserved
Visualisation mode for PLC communication
41 … 59 Reserved, POSICON
60 R stator ident Stator resistance determined by means of measurement P220
61 R rotor ident rotor resistance determined by measurement (P220 Function 2)
stray inductance determined by measurement (P220 Function 2)
63 L stator ident inductance determined by measurement (P220 Function 2)