Pos: 26 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P OS ICON/ S afety [S afety a ußer SK 500 P]/ P40 0 bi s P4 99 ( POS ICO N/ safet y) /P43 4 - Digitalausgang Funk. [SK 500P] ##### "safety" ##### @ 44\mod_1594884776933_388.docx @ 2646570 @ @ 1
P434 Digital out function P
Assignment of functions for the digital output
Value Meaning
Pos: 26 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/POS ICON/ Saf ety [Saf ety auß er SK 500 P]/P4 00 bis P4 99 (POS ICON/ safet y)/P 434 / P48 1 - Funkt ion en D ig itala usg ang _Ei nstel lw ert e [S K 2x xE-F DS, SK 5xx E] ### ## " saf ety ### ## @ 15 \mod_1486118974703_388.docx @ 2318439 @ @ 1
0 Off
For control of a mechanical brake on the motor.
For details see BU 0600
WARNING: Brake failure! The control is not fail-safe! Design the
brake as an operating brake. Ensure that the drive is brought to a
standstill before "STO" becomes active.
General error message.
For details see BU 0600
39 STO inactive This function depicts the reaction of the Safe Pulse Block.
The signal drops (High
Low) when STO and Safe Stop are
Pos: 27 2 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/POS ICON/ Saf ety [Saf ety auß er SK 500 P]/P4 00 bi s P4 99 ( POS ICON /s afet y)/ P48 1 - Fu nkt. Bus IO O ut Bits SK 50 0P ##### + "safety" #### # @ 40\mod_1582035337860_388.docx @ 2590800 @ @ 1
P481 Function BusIO Out bits S
Assignment of functions for Bus IO Out bits. The frequency inverter treats the Bus IO
Out bits as digital outputs.
Value Meaning
Pos: 27 3 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/POS ICON/ Saf ety [Saf ety auß er SK 500P]/P400 bis P499 (POSICON/safety)/P434 / P481 - Funk tio nen Dig ital ausg ang _Ei ns tellw er te [ SK 2x xE- FDS, SK 5x xE] # ### # "s afet y # ### # @ 15\mod_1486118974703_388.docx @ 2318439 @ @ 1
Output not used.
For control of a mechanical brake on the motor.
For details see BU 0600
WARNING: Brake failure! The control is not fail-safe! Design the
brake as an operating brake. Ensure that the drive is brought to a
standstill before "STO" becomes active.
For details see BU 0600
39 STO inactive This function depicts the reaction of the Safe Pulse Block.
The signal drops (High
Low) when STO and Safe Stop are
Pos: 27 5 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/POS ICON/ Saf ety [Saf ety auß er SK 500P]/P400 bis P4 99 ( POS ICON /saf et y)/P 497 - Saf ety Pas sw ort [ SK 5 00P ] @ 44\m od_1594807831341_388.docx @ 2646526 @ @ 1
P497 Safety Password S
- 32768 … 32767
Entry of the password from P498, to unlock the parameters “Safety SS1 max. time”
(P423), “Safe Dig.input” (P424) and “Safety CRC” (P499).
The value which is entered here is lost when the control board of the frequency
inverter is switched off. Password protection is active again.
9.3 "Service and commissioning information"
Pos: 27 6 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 .. .)/POS ICON/ Saf ety [Saf ety auß er SK 500 P]/P4 00 bis P4 99 (POS ICON/ safet y)/P 498 - Saf ety Pas swor t änder n [SK 500 P] @ 41\mod_1588150677885_388.docx @ 2603416 @ @ 1
P498 Change the safety password S
Specification of a password to prevent unauthorised changes to the setting values of
Safety SS1 max. time (P423), Safety Digital Input” (P424) and Safety CRC (P499).
Password protection can be temporarily suspended with Safety Password P497.
The password is cancelled with setting "0".
Pos: 27 7 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par ameter/ Par ameter aufli stung (P000 . ..) /POS ICO N/ Saf ety [Saf ety auß er S K 50 0P ]/P4 00 bis P499 (P OS ICON/ saf ety )/P 499 - Saf ety C RC [SK 500 P] @ 4 1\mod_1588151165841_388.docx @ 2603528 @ @ 1