5 Parameter
BU 0600 en-2319 107
P360 PLC display value
Display range
- 2 147 483.648 … 2 147 483.647
Arrays [-01] … [-05]
Description
Display of PLC data. By means of the relevant process variables, the parameter
arrays can be written by the PLC. The values are not saved!
P370 PLC status
Display range
0000 … FFFF
(hex)
0000 0000 … 1111 1111
(bin)
Description
Display of the actual PLC status.
Display values
Value (Bit) Meaning
0 P350=1
Parameter P350 was set in the "Activate internal PLC" function
1
PLC active
The internal PLC is active.
2 Stop active
The PLC program is in "Stop" status.
3 Debug active
The error checking of the PLC program runs.
4
PLC error
The PLC has an error
However, PLC User Errors 23.xx are not displayed.
5 PLC halted
The PLC program has been halted (Single Step or Breakpoint).
6 Scope Memory used
A function block uses the memory area for the oscilloscope
function of the NORDCON software Because of this, the
oscilloscope function cannot be used.