NORDAC PRO (SK 500P) – Users Manual for Frequency Inverters
34 BU 0600 en-2319
Inverter ID
SK 5xxP
Output choke 3 x 380 ... 480 V
L1 B1 D
Detail: Fastening
Weight
Type
Continuous
current [A]
Inductance
[mH]
L2 B2
0.55 ... 1.5 kW
Material No.:
276996004
4 3 x 3.5 120 104 140 84 75 M6 4 2.8
2.2 ... 4.0 kW
Material No.:
276996009
9 3 x 2.5 155 110 160 130 71.5 M6 4 5.0
5.5 kW
Material No.:
276996017
17 3 x 1.2 185 102 201 170 57.5 M6 10 8.0
Table 12: Output choke data for SK CO1-..., 3~ 480 V
2.4 Line filter
An additional external line filter can be installed into the line supply of the frequency inverter to
maintain the increased noise suppression level (class B as per EN 55011).
2.4.1 Mains filter SK HLD
With a chassis-mounted mains filter, radio interference class B (Class C1)
can be achieved up to a maximum motor cable length of 25 m.
When connecting the mains filter, the "Wiring guidelines" ( Section 2.5.2
and "EMC" ( Section 8.3) must be complied with. In particular, care must
be taken that the pulse frequency is set to the default value (P504). The
mains filter should be placed as close to the side of the frequency inverter as
possible.
The connection is by means of screw connections on the upper (mains) and
lower (inverter) ends of the filter
Inverter ID Filter type [-V/A] L1 B1 D
Detail: Fastening
Connection cross-
section
L2 B2
SK 5xxP-550-340-A…
SK 5xxP-221-340-A
SK HLD 110-500/8 190 45 75 180 20 4
SK 5xxP-301-340-A…
SK 5xxP-551-340-A
SK HLD 110-500/16 250 45 75 240 20 4
mm mm
2
Table 13: Mains filter HLD-...
L1
L2
L3
L3'
L2'
L1'
L2
L1
B2
T
Net z / LI NE
Gerät / LOAD
B1