4 Commissioning
BU 0600 en-2319 63
P200 Motor list:
0 = No change 8 = 0.37kW 400V
1 = No Motor 9 = 0.50PS 460V
2 = 0.25kW 230V 10 = 0.55kW 230V
3 = 0.33PS 230V 11 = 0.75PS 230V
4 = 0.25kW 400V 12 = 0.55kW 400V
5 = 0.33PS 460V 13 = 0.75PS 460V
6 = 0.37kW 230V 14 = 0.75kW 230V
7 = 0.50PS 230V ....
Figure 7: Motor type plate
RECOMMENDATION: For the correct operation of the drive unit, it is necessary to input the
motor data (rating plate) as precisely as possible. In particular, automatic
stator resistance measurement using parameter P220 is recommended.
In order to automatically determine the stator resistance, P220 = 1 must
be set and confirmed by pressing "ENTER". The value calculated for the
line resistance (depending on P207) will be saved in P208.
Motor data for IE2 / IE3 motors are provided via the NORDCON software. With the aid of the "Import
motor parameter" function (also refer to the manual for the NORDCON software BU 0000
), the
required data set can be selected and imported into the frequency inverter.