EasyManua.ls Logo

Nord Drivesystems SK 530P - Minimum Configuration of Control Connections

Nord Drivesystems SK 530P
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORDAC PRO (SK 500P)Users Manual for Frequency Inverters
68 BU 0600 en-2319
4.3 Minimum configuration of control connections
If the frequency inverter is to be controlled via the digital and analogue inputs, this can be
implemented immediately in the condition as delivered. Settings are not necessary for the moment.
Minimum circuitry
Basic parameters
If the current setting of the frequency inverter is not known, loading the default setting is
recommended P523 = 1. The inverter is pre-programmed for standard applications in this
configuration. If necessary the following parameters can be changed with the optional ControlBox
SK TU5-CTR.
P0--
Display
parameters
_ _ _ _ _
P1--
Basic parameters
P2--
Motor data
P4--
Control terminals
P5--
Additional
parameters
P7--
Information
By default the actual
output frequency is displayed
P102
Acceleration time
0 ... 320s
Motor data
P400
Function Analogue input
0...10V frequency
Operating value display
(or operational)
following mains ON
P103
Deceleration time
0 ... 320s
P104
Min. frequency
0 ... 400Hz
P105
Max. frequency
0.1 ... 400Hz
P420
Function Digital input 1
ON right
P523
=1
Load factory data
Potentiometer, 10 kOhm
(Function P400 [-01] = 1)
(min./max. Range = P104/105
Switch, ON/OFF
(Function P420 [-01]= 1)

Table of Contents

Other manuals for Nord Drivesystems SK 530P

Related product manuals