NORDAC SK 750E Manual
122 Technical design subject to change BU 0750 GB
Setting value / Description / Note
Displays the mains voltage being fed to the inverter the moment the inquiry is made.
Displays the torque cacluated the moment the inquiry is made. Calculation will be based on the
motor data entered in parameters P201 …P209.
Displays the strength of the magnetic field in the motor as calculated by the inverter the moment
the inquiry is made. Calculation will be based on the motor data entered in parameters P201
…P209.
Shows which set of parameters is activated at the time.
0 = Parameter set 1
1 = Parameter set 2
2 = Parameter set 3
3 = Parameter set 4
Displays the phase U current measured the moment the inquiry is made.
Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
Displays the phase V current at the moment the inquiry is made.
Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
Displays the phase W current at the moment the inquiry is made.
Hinweis: Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
Displays the current speed supplied by the shaft encoder.
Displays the current d.c. link voltage.
P740 ... - 01
...
... - 06
This parameter provides information on the control
word currently being used and on the setpoints be-
ing transmitted via the bus systems.
... - 01 = control word
... - 02 = setpoint 1 (P546)
... - 03 = setpoint 1 high byte
... - 04 = setpoint 2 (P547)
... - 05 = setpoint 3 (P548)
... - 06 = Bus-In bit (P546-P548)