NORDAC SK 750E Manual
122 Technical design subject to change BU 0750 GB
Parameter
Setting value / Description / Note
Parameter
set
Available with option
P728
Input Voltage
Always available
0 ... 1000 V
Displays the mains voltage being fed to the inverter the moment the inquiry is made.
P729
Torque
Always available
-400 ... 400 %
Displays the torque cacluated the moment the inquiry is made. Calculation will be based on the
motor data entered in parameters P201 …P209.
P730
Field
Always available
0 ... 100 %
Displays the strength of the magnetic field in the motor as calculated by the inverter the moment
the inquiry is made. Calculation will be based on the motor data entered in parameters P201
…P209.
P731
Parameter set
Always available
0 ... 3
Shows which set of parameters is activated at the time.
0 = Parameter set 1
1 = Parameter set 2
2 = Parameter set 3
3 = Parameter set 4
P732
Phase U current
Always available
0.0 ... 500.0 A
Displays the phase U current measured the moment the inquiry is made.
Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
P733
Phase V current
Always available
0.0 ... 500.0 A
Displays the phase V current at the moment the inquiry is made.
Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
P734
Phase W current
Always available
0.0 ... 500.0 A
Displays the phase W current at the moment the inquiry is made.
Hinweis: Note: Due to the measuring method this value may be slightly different from the value displayed
in P719 even when the output currents are symmetrical.
P735
Speed encoder
ENC
POS
-9999 ... +9999 rpm
Displays the current speed supplied by the shaft encoder.
P736
D.c. link voltage
Always available
0 ... 1000 V DC
Displays the current d.c. link voltage.
P740 ... - 01
...
... - 06
PZD bus in 1...6
Always available
0 ... FFFF hex
This parameter provides information on the control
word currently being used and on the setpoints be-
ing transmitted via the bus systems.
... - 01 = control word
... - 02 = setpoint 1 (P546)
... - 03 = setpoint 1 high byte
... - 04 = setpoint 2 (P547)
... - 05 = setpoint 3 (P548)
... - 06 = Bus-In bit (P546-P548)