3.3 Overview of the customer interfaces
BU 0750 GB Technical design subject to change 43
3.3.5 Multi I/O custom interface
(SK CU1-MLT, part no.: 278200010)
Maximum enhancement of the SK 750E in terms of digital and
analogue signal processing is enabled if the Multi I/O custom inter-
face (Customer Unit) is used. It will add 2 analogue and 6 digital
inputs to the basic equipment of the inverter. The two analogue in-
puts are capable of processing signals in the range between 0 and
10V, 0 and 20mA (4 and 20mA) or -10V and +10V respectively.
Two programmable and scalable analogue outputs 0...10V enable
current operating parameters to be retransmitted to a read-out de-
vice or to a process control system.
The two relay contacts can be used for brake control or to transmit
an alarm signal to another system.
The digital inputs of the Multi I/O are not capable of processing
analogue setpoints! (See also the section on "Control terminals",
P420-P425)
NOTE: All control voltages are related to a common reference potential!
The potentials AGND /0V and GND /0V of the various units are interconnected.
Maximum allowable current load of the 5/15V power sources combined = 300mA!
SPC analogue output:
0...10V / -10...+10 V
or potentiometer: 2...10k
Floating contact or output
of an SPC: 7.5...33V
Output relays:
2.0A max.
28V DC /230 V AC
Analogue inputs 1 and 2:
-10...+10V, 0/4...20mA
Analogue outputs 1 and 2:
0...10V / 5mA max.
U
REF
= 10 V / I
max
= 10 mA
DIG IN 6 exclusively =
temperature sensor!
Switching threshold = 2.5 V
Digital inputs:
DIG IN 1 = enable right
DIG IN 2 = enable left
DIG IN 3 = parameter set bit 0
DIG IN 4 = fixed frequency 1
DIG IN 5 / 6 = without function
Funktion
X2.1
X2.2
X2.3
11 VREF 10V
12 AGND /0V
14 AIN1 +
16 AIN2 +
17 AOUT1
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
24 DIG IN 4
42 VO +15V
01 REL1.1
02 REL1.2
03 REL2.1
04 REL2.2
25 DIG IN 5
26 DIG IN 6
18 AOUT2
40 GND /0V
41 VO +5V
Burden for connection into circuit of
0/4...20mA analogue input 1 (250 )
Burden for connection into circuit of
0/4...20mA analogue input 2 (250 )
IN / OUT ana-
logue signals
Analogue input 1
ON = curr., OFF = volt.
Analogue input 2
ON = curr., OFF = volt.
U/I changeover, R = 250 Ω