96 Technical design subject to change BU 0750 GB
Setting value / Description / Note
Adjustable digital low-pass filter for the analogue signal
Pulse spikes are filtered out, reaction time is prolonged.
This parameter is identical with P400.
0 = 0 – 10V limited
1 = 0 – 10V
2 = 0 – 10V controled
3 = - 10V – 10V
This parameter is the same as P401. P402/403 change into P407/408.
This parameter is identical with P402.
This parameter is identical with P403.
This parameter is identical with P404.
-400.0...400.0 Hz
[ 0.0 ]
Is the minimum frequency which may affect the principal setpoint through secondary setpoints.
The term secondary setpoint is applied to any of the frequencies which are additionally supplied to
the FI so that more functions can be executed:
PID actual frequency frequency addition
frequ. Subtraction bus-transmitted secondary setpoints
process controller min. frequency via an analogue setpoint (potentiometer)
-400.0...400.0 Hz
[ 50.0 ]
Is the maximum frequency which may affect the principal setpoint through secondary setpoints.
The term secondary setpoint is applied to any of the frequencies which are additionally supplied to
the FI to enable more functions to be executed:
PID actual frequency frequency addition
frequency subtraction bus-transmitted secondary setpoints
max. frequency via an analogue setpoint (potentiometer)
process controller