EasyManua.ls Logo

Nord Drivesystems SK PAR-3H - Operating Mode IO-C (Control Mode Via DI1;DO1 of the SK 2 Xxe)

Nord Drivesystems SK PAR-3H
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORDAC Control and Parameter Boxes
46 Subject to technical alterations BU 0040 GB-1611
3.1.3.2 Operating mode IO-C (Control mode via DI1/DO1 of the SK 2xxE)
In the operating mode IO-C, communication is via digital input "1" and digital output "1" of the frequency inverter.
Here, all the features provided by the SimpleBox SK CSX-3H/ -3E (Section 2.2) are also available.
Field of use
In this operating mode, the box can communicate with SK 2xxE series frequency inverters with firmware version V
1.3 or higher (see parameter (P707[-01])).
Functions
In this operating mode the functions
Parameterisation
Control
Display of operating values
are available without restriction and correspond to those of the SimpleBox SK CSX-3H/ -3E. For technical reasons,
the display and the key reaction times are somewhat increased.
Connections
Connection to the horizontal terminal bar is by means of a
4-wire cable.
Settings on the frequency inverter
Name Parameter number Value Notes
Function, digital output 1 P434 [-01] {00} or {07}* Setting {07} corresponds to the default value
* Other settings are not permissible and result in the loss of communication between the Simple Setpoint Box and the frequency inverter in IO-C mode.
NOTE
In "IO-C" mode, the parameterised functions of the IOs "Digital Input 1 (parameter (P420[-01]))
and "Digital Output 1" (parameter (P434[-01])) are deactivated. The condition for this is that
Digital Output 1 is parameterised either to "No function" {00} or the default setting "Fault" {07}.
The DIP switch S1: 3 … 5 of the frequency inverter ("BUS" / "IO") must be left in the factory
setting ("OFF" or"0") in order to prevent communication faults on the frequency inverter.
44 24V
DC
40 GND
B1 Signal OUT
C1 Signal IN
24V
GND/0V
44 40 B1 C1
Connection of the 24V power supply
from the SK 2xxE
I/O connection for FI setpoint values
IN
OUT
Connection for IO-C mode
SK SSX-3A
SK 2xxE-
44 40 21 1
I/O connection for actual FI values