5 Parameters
BU 0505 EN-3021 103
No motor: In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. The
following motor data is set here: 50.0 Hz / 1500 rpm / 15.0 A / 400 V / 0.00 kW / cos
ϕ
S
Ω
LEER
0.25kW 230V
4.0 kW 230V
90.0 kW 400V
1.00kW 115V
0.37kW 230V
5.5 kW 230V
132.0 kW 400V
1.10kW 230V 90T1/4
0.55kW 230V
7.5 kW 230V
200.0 kW 400V
1.50kW 230V 90T1/4
14 = 0.75kW 230V 44 = 11.0 kW 400V 74 = 11.0 kW 230V 104 = 2.20kW 230V 90T3/4
18 = 1.1 kW 230V 48 = 18.5 kW 400V 78 = 18.5 kW 230V 108 = 3.00kW 230V 100T2/4
Pos: 150 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200-P299/Parameter P201 – Motor Nennfre quenz @ 0\mod_132758838592 3_388.docx @ 7884 @ @ 1
P201
Nominal motor frequency
(Nominal motor frequency)
S P
10.0 ... 399.9 Hz
{ see information }
The motor nominal frequency determines the V/f break point at which the FI supplies the nominal
voltage (P204) at the output.
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 151 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P202 – Motor Nenndrehzahl @ 0\mod_132758 8441470_388.doc x @ 7907 @ @ 1
P202
Nominal motor speed
(Nominal motor speed)
S P
150 ... 24000 rpm
{ see information }
The nominal motor speed is important for the correct calculation and control of the motor slip and
the speed display (P001 = 1).
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 152 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P203 – Motor Nennstrom @ 0\mod_132758850 0455_388.docx @ 7930 @ @ 1