SK 54xEUsers Manual for Frequency Inverters
168 BU 0505 EN-3021
10.4 Init error Option
Bus module initialisation failure
Check Bus module power supply.
DIP switch setting of a connected I/O extension
module is incorrect
Check P746.
Bus module not correctly plugged in.
10.1 System error option
Bus module system error
Further details can be found in the respective
supplementary Bus operating instructions.
I/O Extension:
Incorrect measurement of the input voltage or
undefined provision of the output voltages due to an
error in the reference voltage generation
Short-circuit in analog output
10.3
10.5
10.6
10.7
10.8 Option error
External module communication failure
Connection fault / error in the external module
Brief interruption (<1sec) of the 24 V supply of the
internal CAN/CANopen bus
10.9 Module missing / P120
The module entered in parameter (P120) is not available.
Check connections
Pos: 461 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E011 [ SK 180E ... SK 5xxE] @ 2\mod_1347 453318765_388.doc x @ 46626 @ @ 1
E011
11.0 Customer interface
Error in analog-digital converter
Internal customer unit (internal data bus) faulty or
damaged by radio radiation (EMC)
Check control terminals connection for short-circuit.
Minimize EMC interference by laying control and
power cables separately.
Earth the devices and shields well.
Pos: 462 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E012 [ SK 5xxE] @ 2\mod_136152418654 7_388.docx @ 59066 @ @ 1
E012
12.0 External watchdog
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
Check connections
Check P460 setting
12.1 Motor limit
"Motor switch-off limit"
The motor switch-off limit P534 [-01] has triggered.
Reduce load on motor
Set higher value in (P534 [-01]).
12.2 Generator limit
"Generator switch-off limit"
The generator switch-off limit P534 [-02] has triggered.
Reduce load on motor
Set higher value in (P534 [-02]).
12.5 Load limit
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
Adjust load.
Change limit values ((P525) ... (P527)).
Increase delay time (P528).
Change monitoring mode (P529).
12.8 Analog In minimum
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"
12.9 Analog In maximum
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"