6 Operating status messages
BU 0505 EN-3021 169
E013
13.0 Encoder error
No signal from encoder
• Check 5V sensor if present.
• Check supply voltage of encoder.
13.1 Speed slip error
"Speed slip error"
The slip speed error limit was reached.
• Increase setting in P327.
13.2 Shut-down monitoring
The slip error monitoring has triggered; the motor could not
follow the setpoint.
• Check motor data P201-P209! (Important for the
current controller)
• Check motor circuit.
• In servo mode, check the encoder setting P300 and
check the following
• Increase setting value for torque limit in P112.
• Increase setting value for current limit in P536.
• Check deceleration time P103 and extend if
necessary
13.5 Reserved
Error message for POSICON see supplementary
instructions
13.6 Reserved
Error message for POSICON see supplementary
instructions
Pos: 464 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E014 "r eserviert" [SK 200E ... SK 5xxE] @ 2\mod_1347 454273854_388.doc x @ 46776 @ @ 1
E014
--- Reserved
Error message for POSICON see supplementary
instructions
Pos: 465 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E015 [ SK 180E ... SK 5xxE] @ 2\mod_13474542780 51_388.docx @ 46801 @ @ 1
E015
--- Reserved
Pos: 466 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E016 [ SK 135E ... SK 5xxE] @ 2\mod_13474542806 25_388.docx @ 46826 @ @ 1
E016
16.0 Motor phase error
A motor phase is not connected.
•
Check P539
•
Check motor connection
16.1 Magnetisation current
monitoring
"Magnetisation current
monitoring"
Required exciting current not achieved at moment of switch-
on.
•
Check P539
• Check motor connection
Pos: 467 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E017 "Kunde nschnittste lle gestört" [SK 5xxE] @ 6\mod_1416234895196_3 88.docx @ 186366 @ @ 1
E017
17.0 Customer interface fault
• EMC fault
• Defective component
Pos: 468 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E018 "r eserviert" [SK 2xxE/SK 5xxE] @ 2\mod_13 47454282777_388.doc x @ 46851 @ @ 1
E018
18.0 Reserved
Error message for "Safe Pulse Block" see supplementary
instructions
Pos: 469 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E019 [ SK 180E/SK 2xxE/SK 5xxE] @ 2\mod_1347454285 788_388.docx @ 46876 @ @ 1
E019
19.0 Parameter identification
"Parameter identification"
Automatic identification of the connected motor was
unsuccessful
• Check motor connection
• Check preset motor data (P201 … P209)
• PMSM – CFC Closed Loop Operation: Rotor position
of motor incorrect in relation to incremental encoder
Perform determination of rotor position (initial enable
after a "Mains on" only with motor stationary (P330)
19.1 Star / Delta circuit incorrect
"Motor star / delta circuit
incorrect"
Pos: 470 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E020 / E021 [SK 135E ... SK 5xxE] @ 2\mod_13474542 88768_388.docx @ 46901 @ @ 1