E013
13.0 Encoder error
No signal from encoder
Check 5V sensor if present.
Check supply voltage of encoder.
13.1 Speed slip error
"Speed slip error"
The slip speed error limit was reached.
Increase setting in P327.
13.2 Shut-down monitoring
The slip error monitoring has triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! (Important for the
current controller)
Check motor circuit.
In servo mode, check the encoder setting P300 and
check the following
Increase setting value for torque limit in P112.
Increase setting value for current limit in P536.
Check deceleration time P103 and extend if
necessary
13.5 Reserved
Error message for POSICON see supplementary
instructions
13.6 Reserved
Error message for POSICON see supplementary
instructions
Pos: 464 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E014 "r eserviert" [SK 200E ... SK 5xxE] @ 2\mod_1347 454273854_388.doc x @ 46776 @ @ 1
E014
--- Reserved
Error message for POSICON see supplementary
instructions
Pos: 465 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E015 [ SK 180E ... SK 5xxE] @ 2\mod_13474542780 51_388.docx @ 46801 @ @ 1
E015
--- Reserved
Pos: 466 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E016 [ SK 135E ... SK 5xxE] @ 2\mod_13474542806 25_388.docx @ 46826 @ @ 1
E016
16.0 Motor phase error
A motor phase is not connected.
Check P539
Check motor connection
16.1 Magnetisation current
monitoring
"Magnetisation current
monitoring"
Required exciting current not achieved at moment of switch-
on.
Check P539
Check motor connection
Pos: 467 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E017 "Kunde nschnittste lle gestört" [SK 5xxE] @ 6\mod_1416234895196_3 88.docx @ 186366 @ @ 1
E017
17.0 Customer interface fault
EMC fault
Defective component
Pos: 468 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E018 "r eserviert" [SK 2xxE/SK 5xxE] @ 2\mod_13 47454282777_388.doc x @ 46851 @ @ 1
E018
18.0 Reserved
Error message for "Safe Pulse Block" see supplementary
instructions
Pos: 469 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E019 [ SK 180E/SK 2xxE/SK 5xxE] @ 2\mod_1347454285 788_388.docx @ 46876 @ @ 1
E019
19.0 Parameter identification
"Parameter identification"
Automatic identification of the connected motor was
unsuccessful
Check motor connection
Check preset motor data (P201 … P209)
PMSM CFC Closed Loop Operation: Rotor position
of motor incorrect in relation to incremental encoder
Perform determination of rotor position (initial enable
after a "Mains on" only with motor stationary (P330)
19.1 Star / Delta circuit incorrect
"Motor star / delta circuit
incorrect"
Pos: 470 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E020 / E021 [SK 135E ... SK 5xxE] @ 2\mod_13474542 88768_388.docx @ 46901 @ @ 1