6 Operating status messages
BU 0505 EN-3021 171
2.1 Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))
• Reduce motor load
• Increase motor speed
2.2 Overtemp. Brake r.ext
"Overtemperature of external
brake resistor "
Overtemperature via digital
input (P420 […])={13}
Warning: Temperature monitor (e.g. brake resistor) has
activated
• Digital input is Low
Pos: 478 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Warnung C003 [S K 180E ... SK 5xxE] @ 2\mod_1347457 006237_388.doc x @ 47199 @ @ 1
C003
3.0 Overcurrent, I
2
t limit
Warning: Inverter: I
2
t limit has triggered, e.g. > 1.3 x I
n
for
60s (please also note P504)
• Continuous overload at FI output
3.1 Overcurrent, chopper I
2
t
Warning: I
2
t limit for the brake chopper has triggered, 1.3x
value attained for 60s (also note P554, if present, as well as
P555, P556, P557)
• Avoid overload of brake resistance
3.5 Torque current limit
Warning: Torque current limit reached
•
Check (P112)
3.6 Current limit
Warning: Current limit reached
• Check (P536)
Pos: 479 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Warnung C004 [S K 180E ... SK 5xxE] @ 2\mod_1347457 006705_388.doc x @ 47224 @ @ 1
C004
4.1 Overcurrent measurement
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
• FI is overloaded
• Drive sluggish, insufficiently sized
• Ramps (P102/P103) too steep -> Increase ramp time
• Check motor data (P201 … P209)
• Switch off slip compensation (P212)
Pos: 480 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Warnung C008 [S K 180E ... SK 5xxE] @ 2\mod_1347457 201563_388.doc x @ 47249 @ @ 1
C008
8.0 Parameter loss
Warning: One of the cyclically saved messages such
as operating hours or enabling time could not be
saved successfully.
The warning disappears as soon as saving can be
Pos: 481 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Aufli stung)/Warnung C012 [ SK 5xxE] @ 2\mod_1361539953 134_388.docx @ 59296 @ @ 1
C012
12.1 Motor Limit / Customer
"Motor switch-off limit"
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2 Generator limit
"Generator switch-off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.5 Load monitor
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).
Pos: 482 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Me ldungen Einschaltsper re (Tabellenübersc hrift) @ 3\mod_13618034 67385_388.doc x @ 59922 @ 5 @ 1