EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 182

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SK 54xEUsers Manual for Frequency Inverters
182 BU 0505 EN-3021
Frequency inverter type SK 5xxE…
-301-340- -401-340- -551-340- -751-340-
Size
3 3 4 4
Nominal motor power
(4-pole standard motor)
400 V
3.0 kW 4.0 kW 5.5 kW 7.5 kW
480 V
4 hp 5 hp 7½ hp 10 hp
Mains voltage
400 V
3 AC 380 … 480V, -20% / +10%, 47 … 63 Hz
Input current
rms
10.5 A 13.3 A 17.5 A 22.4 A
FLA
10.5 A 13.3 A 17.5 A 22.4 A
Output voltage
400 V
3 AC 0 - Mains voltage
Typical output
rms
7.5 A 9.5 A 12.5 A 16 A
FLA
6.7 A 8.5 A 11 A 14 A
Min. brake resistor Accessories
91 74 60 44
Pulse frequency
range
3 16 kHz
Factory setting
6 kHz
Ambient temperature S1
40 °C. 40 °C. 40 °C. 40 °C.
S3 80 %, 10 min
- - 50 °C. 50 °C.
S3 70 %, 10 min
50 °C. 50 °C. 50 °C. 50 °C.
Type of ventilation
Fan cooling, temperature-controlled
switching thresholds:
1)
ON= 57°C OFF=47°C
Weight Approx. [kg]
2.7 3.1
General fuses (AC) (recommended)
slow-blowing
16 A 16 A 20 A 25 A
Isc
2)
[A]
UL fuses (AC) permitted
Class
5 000
10 000
100 000
Fuse
J (600 V) x
12 A 15 A 20 A 25 A
CC, J, R, T, G, L (600 V)
x
25 A 30 A 30 A 30 A
Bussmann LPJ-
x
12SP 15SP 20SP 25SP
CB
(480 V)
x
25 A 25 A 25 A 25 A
1) Brief test run after application of the mains voltage (for SK 5x5 inverters after application of the control voltage)
2) Maximum permissible mains overload current

Table of Contents

Related product manuals