EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 184

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SK 54xEUsers Manual for Frequency Inverters
184 BU 0505 EN-3021
Frequency inverter type SK 5xxE…
-302-340- -372-340- -452-340- -552-340- -752-340-
Size
7 7 8 8 9
Nominal motor power
(4-pole standard motor)
400 V
30.0 kW 37.0 kW 45.0 kW 55.0 kW 75.0 kW
480 V
40 hp 50 hp 60 hp 75 hp 100 hp
Mains voltage
400 V
3 AC 380 … 480V, -20% / +10%, 47 … 63 Hz
Input current
rms
84 A 105 A 126 A 154 A 210 A
FLA
64.1 A 80 A 108 A 134 A 174 A
Output voltage
400 V
3 AC 0 - Mains voltage
Typical output
rms
60 A 75 A 90 A 110 A 150 A
FLA
52 A 68 A 77 A 96 A 124 A
Min. brake resistor Accessories
9 9 8 8 6
Pulse frequency
range
3 16 kHz 3 – 8 kHz
Factory setting
6 kHz 4 kHz
Ambient temperature S1
40 °C. 40 °C. 40 °C. 40 °C. 40 °C.
S3 80 %, 10 min
- - - - -
S3 70 %, 10 min
- - - - -
Type of ventilation
Fan cooling, temperature-controlled
switching thresholds:
1)
ON= 57°C OFF=47°C ON= 56°C OFF=52°C
Fan speed control
between 47°C (52°C) and approx. 70°C
2)
Weight Approx. [kg]
16 20 25
General fuses (AC) (recommended)
slow-blowing
100 A 125 A 160 A 160 A 224 A
Isc
3)
[A]
UL fuses (AC) permitted
Class
10 000
65 000
100 000
Fuse
RK5 (480 V) x
- - 125 A 150 A 200 A
CC, J, R, T, G, L (600 V)
x
100 A 100 A 125 A 150 A 200 A
- - - - -
CB
(480 V) x x
- - 125 A 150 A 200 A
(480 V) x
100 A 100 A - - -
1) Short test run after connection of the mains voltage or control voltage
2) In case of overload of the frequency inverter, the speed of the fan is increased to 100% regardless of the actual temperature of the device.
3) Maximum permissible mains overload current

Table of Contents