7 Technical data
BU 0505 EN-3021 185
Device type (Size 910 11): SK 5xxE…
-902-340- -113-340- -133-340- -163-340-
Size
9 10 10 11
Nominal motor power
(4-pole standard motor)
400 V
90.0 kW 110.0 kW 132.0 kW 160.0 kW
480 V
125 hp 150 hp 180 hp 220 hp
Mains voltage
400 V
3 AC 380 … 480V, -20% / +10%, 47 … 63 Hz
Input current
rms
252 A 308 A 364 A 448 A
FLA
218 A 252 A 300 A 370 A
Output voltage
400 V
3 AC 0 - Mains voltage
Output current
rms
180 A 220 A 260 A 320 A
FLA
156 A 180 A 216 A 264 A
Min. brake resistor Accessories
6 3.2 3.0 2.6
Pulse frequency
range
3 – 8 kHz
Factory setting
4 kHz
Ambient temperature S1
40 °C. 40 °C. 40 °C. 40 °C.
S3 80 %, 10 min
- - - -
S3 70 %, 10 min
- - - -
Type of ventilation
Fan cooling, temperature-controlled
switching thresholds:
1)
ON= 56°C OFF=52°C
Fan speed control
Between
52°C and
approx.
70°C
2)
there is no speed control!
3)
Weight Approx. [kg]
30 46 49 52
General fuses (AC) (recommended)
slow-blowing
315 A 350 A 350 A 400 A
Isc
4)
[A]
UL fuses (AC) permitted
Class
10 000
18 000
65 000
100 000
Fuse
RK5 (480 V) x
250 A - - -
J (480 V) x
- 350 A 350 A -
J (480 V)
x
- - - 400 A
CC, J, R, T, G, L (600 V)
x
250 A 350 A 350 A 400 A
CB
(480 V) x
x
250 A - -
-
1) Short test run after connection of the mains voltage or control voltage
2) In case of overload of the frequency inverter, the speed of the fan is increased to 100 % regardless of the actual temperature of the device.
3) The fans switch on sequentially (interval approx. 1.8 sec)
4)
Maximum permissible mains overload current