SK 54xEUsers Manual for Frequency Inverters
192 BU 0505 EN-3021
Frequency inverter
Setpoint of pilot machine
AIN 1
Enable right
DIN 1
Actual position CR
AIN 2
Nominal position CR via
parameter P412
Pos: 500 /Anleitungen/ Elektronik/F U und Starter/9. Zusatzinf ormationen [BU 0500 / BU 0200] /Prozessregler/P arametereinste llungen Prozessregler [SK 5xxE] @ 0\mod_132818708 9203_388.docx @ 14213 @ 35 @ 1
8.2.2 Process controller parameter settings
Example: SK 500E, setpoint frequency: 50 Hz, control limits: +/- 25%
P105 (maximum frequency)
[Hz]
[
]
[ ] [ ]
×
+
100%
Hz
%P415Hzq.Setpointfr
q.Setpointfr
Example:
=
×
+
%100
%2550
50
Hz
Hz
62.5Hz
P400 (Funct. analog input): „4“ (frequency addition)
P411 (setpoint frequency) [Hz]
Set frequency with 10 V at analog input 1
Example: 50 Hz
P412 (Process controller
setpoint):
CR middle position / Default setting 5V (adjust if necessary)
P413 (P controller) [%]: Factory setting 10% (adjust if necessary)
P414 (I-controller) [% / ms]: recommended 100%/s
P415 (limitation +/-) [%]
Controller limitation (see above)
Note:
In the function process controller, parameter P415 is used as a
controller limiter downstream from the PI controller. This
parameter therefore has a double function.
Example: 25% of setpoint
P416 (ramp before controller)
[s]:
Factory setting 2s
(if necessary, adjust to match controller
behaviour)
P420 (Funct. digital input 1): "1" Enable right
P405 (Funct. Analoginput 2): „14“ actual value PID process controller
Controller limit
P415 in % of
setpoint
Controller limit
P415
f
t