8.2.2 Process controller parameter settings
Example: SK 500E, setpoint frequency: 50 Hz, control limits: +/- 25%
[Hz]
[
]
[ ] [ ]
×
+≥
100%
Hz
%P415Hzq.Setpointfr
q.Setpointfr
Example:
62.5Hz
P400 (Funct. analog input): „4“ (frequency addition)
P411 (setpoint frequency) [Hz]
Set frequency with 10 V at analog input 1
Example: 50 Hz
setpoint):
CR middle position / Default setting 5V (adjust if necessary)
P413 (P controller) [%]: Factory setting 10% (adjust if necessary)
P414 (I-controller) [% / ms]: recommended 100%/s
P415 (limitation +/-) [%]
Controller limitation (see above)
Note:
In the function process controller, parameter P415 is used as a
controller limiter downstream from the PI controller. This
parameter therefore has a double function.
Example: 25% of setpoint
P416 (ramp before controller)
[s]:
Factory setting 2s
(if necessary, adjust to match controller
behaviour)
P420 (Funct. digital input 1): "1" Enable right
P405 (Funct. Analoginput 2): „14“ actual value PID process controller
Controller limit
P415 in % of
setpoint