8 Additional information
BU 0505 EN-3021 195
Inverter type
DIP: "EMC-Filter"
(chapter 2.9.2)
150 kHz - 30 MHz
Class C2 Class C1
SK 5xxE-250-323-A … SK 5xxE-401-323-A
3 – 2 20 m 5 m
3 – 3 5 m -
SK 5x5E-551-323-A … SK 5x5E-182-323-A 4 – 2 20 m -
SK 5xxE-550-340-A … SK 5xxE-751-340-A
SK 5xxE-550-340-A … SK 5xxE-751-340-A
+ suitable bottom-mounted combination filter
SK NHD-…
3 – 2 100 m 50 m
SK 5xxE-550-340-O … SK 5xxE-751-340-O
+ suitable bottom-mounted combination filter
SK NHD-…
3 – 2 100 m 25 m
SK 5x5E-112-340-A … SK 5x5E-372-340-A
SK 5x5E-112-340-A … SK 5x5E-372-340-A
+ suitable bottom -mounted SK LF2-…
4 – 2 100 m 50 m
SK 5x5E-112-340-O … SK 5x5E-372-340-O
+ suitable bottom -mounted SK LF2-…
4 – 2 100 m 25 m
SK 5x5E-452-340-A … SK 5x5E-163-340-A
Table 38: EMC, max. shielded motor cable length with regard to compliance with the limit value classes
Pos: 501.7 /Anleitung en/Elektronik/F U und Starter/8. /9. Zusatzinformationen [BU 0500 / BU 0200]/EMV/_EMV des Ger ätes _ Grenzwertklassen @ 2\m od_1347443407776_3 88.docx @ 46088 @ @ 1
EMC overview of standards that are used in accordance with EN 61800-3
as checking and measuring procedures:
Cable-related emission
(interference voltage)
EN 55011
Radiated emission
(interference field strength)
EN 55011
Interference immunity EN 61000
-6-1, EN 61000-6-2
ESD, discharge of static electricity
EMF, high frequency electro-magnetic
fields
EN 61000-4-3 10 V/m; 80 – 1000 MHz
Burst on mains and motor cables
Surge (phase-phase / phase-ground)
Cable-led interference due to high
frequency fields
EN 61000-4-6 10 V, 0.15 – 80 MHz
Voltage fluctuations and drops
Voltage asymmetries and frequency
changes
EN 61000-2-4 3 %; 2 %
Table 39: Overview according to product standard EN 61800-3