EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 26

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SK 54xEUsers Manual for Frequency Inverters
26 BU 0505 EN-3021
Size valid description
5 - 6 For 240 V
models only:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical
Amperes, 240 Volts Maximum.”
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 65000 rms Symmetrical
Amperes, 240 V Maximum When Protected By CC, J, T or R Class Fuses or When Protected
By A Circuit Breaker Having An Interrupting Rating Not Less Than 65000 rms Symmetrical
Amperes, 240 Volts Maximum.”
“The specific fuse/circuit breaker sizes for each models are shown in
1)
. Voltage rating of the
fuses and circuit breakers must at least be suitable for the input voltage.”
For 480 V
models only:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical
Amperes, 480 Volts Maximum.”
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 65000 rms Symmetrical
Amperes, 480 V Maximum When Protected By CC, J, T or R Class Fuses or When Protected
By A Circuit Breaker Having An Interrupting Rating Not Less Than 65000 rms Symmetrical
Amperes, 480/277 Volts Y Maximum.”
“The specific fuse/circuit breaker sizes for each models are shown in
1)
. Voltage rating of the
fuses and circuit breakers must at least be suitable for the input voltage.”
“480V models only for use in WYE 480/277V source, when protected by Circuit Breakers.”
For 500 V
models only:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical
Amperes, 500 Volts Maximum.”
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 65000 rms Symmetrical
Amperes, 500 V Maximum When Protected By CC, J, T or R Class Fuses or When Protected
By A Circuit Breaker Having An Interrupting Rating Not Less Than 65000 rms Symmetrical
Amperes, 480/277 Volts Y Maximum.”
“The specific fuse/circuit breaker sizes for each models are shown in
1)
. Voltage rating of the
fuses and circuit breakers must at least be suitable for the input voltage.”
“480V models only for use in WYE 480/277V source, when protected by Circuit Breakers.”
7 For 240 V
models only:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 000 rms Symmetrical
Amperes, 240 Volts Maximum, When Protected by High-
Interrupting Capacity, Current Limiting
Class CC, G, J, L, R, T, etc. Fuses”. The specific fuse ratings are shown in
1)
.
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 65 000 rms Symmetrical
Amperes, 240 Volts Maximum, When Protected by A Circuit Breaker Having An Interrupting
Rating Not Less Than 65 000 rms Symmetrical Amperes, 480 Volts Maximum”. The specific
Circuit Breaker ratings are shown in
1)
.
For 480 V
models only:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 000 rms Symmetrical
Amperes, 480 Volts Maximum, When Protected by High-
Interrupting Capacity, Current Limiting
Class CC, G, J, L, R, T, etc. Fuses”. The specific fuse ratings are shown in
1)
.
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 65 000 rms Symmetrical
Amperes, 480 Volts Maximum, When Protected by A Circuit Breaker Having An Interrupting
Rating Not Less Than 65 000 rms Symmetrical Amperes, 480 Volts Maximum”. The specific
Circuit Breaker ratings are shown in
1)
.

Table of Contents