2 Assembly and installation
BU 0505 EN-3021 33
Assembly
For installation, a hole with the size of the heat sink must be made in the wall of the control cabinet
(note the load bearing capacity).
1. Apply heat-conducting paste to the ColdPlate of the
SK 5xxE;
2. firmly fasten the heat sink to the ColdPlate with the
4 enclosed screws;
3. remove any heat conducting paste which exudes;
4. Place the seal between the frequency inverter and
the wall of the control cabinet (inside of the control
cabinet);
5. Insert the frequency inverter and guide the external
heat sink out of the control cabinet through the hole
in the wall of the control cabinet;
6. Fasten the frequency inverter to the wall of the
control cabinet though all of the 6 or 8 holes in the
ColdPlate.
Protection class IP54
With correct installation, the control cabinet achieves IP54 from the outside at the point of installation.
Pos: 43 /Anleitungen/ Elektronik/FU und St arter/2. Montage und Inst allation/Zubehör/ 2.4 Hutschienenmo ntageset SK DRK1-... [BU 0500] @ 0\mod_1325861903944_38 8.docx @ 5802 @ 255 @ 1
Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korrekte Datei und den korrekten Speicherort zeigt.
Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korrekte Datei und den korrekten Speicherort zeigt.
Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korrekte Datei und den korrekten Speicherort zeigt.
Das verknüpfte Bild kann nicht angezeigt werden. Möglicherweise wurde die Datei verschoben, umbenannt oder gelöscht. Stellen Sie sicher, dass die Verknüpfung auf die korrekte Datei und den korrekten Speicherort zeigt.